Claims that power is the top cost are wrong: using a 5% amortization and zero residual shows fully burdened power is #2 while servers (54% of monthly cost) dominate today, distribution loss is ~11%, and average utilization sits at 10–15%. A market product named spot instance sells idle capacity into valleys and demonstrably flattens demand. Cooling fixes—hot‑aisle containment, higher inlet temps (ASHRAE to 81–90°F), exhausts >100°F and open the damn window economization—cut huge costs. Networking shifts via OpenFlow and commodity ASICs promise cheaper, flexible switching.